FY 2024–25 baseline — investment-grade

Framed as an ASHRAE Standard 211 Level 3 investment-grade energy audit. Adjusted-baseline regression uses IPMVP Option B (retrofit isolation, all parameters) with cross-checks under Option D (calibrated simulation). Statistical acceptance is enforced against ASHRAE Guideline 14.

ASHRAE 211 · Level 3IPMVP Option BIPMVP Option D · cross-checkGuideline 14 · Table 5-2
Regression fit

Model summary

MetricValueG14 thresholdStatus
CV(RMSE) — hourly12.4%30%✓ PASS
NMBE — hourly (signed)-2.1%|·| ≤ 10%✓ PASS
0.914indicativestrong fit
Annual baseline energy3.84 GWh₹64.20 L/yrreference
Standard error (annual)138.0 MWh2·SE ≈ 276.0 MWhused in IPMVP significance test
Overall verdict: ✓ Model accepted under Guideline 14 hourly criteria
Governance

Baseline freeze

PeriodFY 2024–25 (Apr 2024 → Mar 2025)
MethodIPMVP Option B
Audit levelASHRAE Std 211 Level 3
Frozen byCleteco Analyst — R. Menon
Frozen at2025-04-01T09:12:33+05:30
Hash0x8f2a1d0e6b4c93f5e7a2b18c4d5e6f7a8b9c0d1e2f3a4b5c6d7e8f9a0b1c2d3
Regression coefficients

Independent variables & fit

Independent variables: Outside-air temperature (°C, hourly) · Occupancy fraction (0–1, hourly)

VariableCoefficientUnitsp-valueNote
Intercept118.60kWh/hr<0.001Base plant draw at 0 load reference.
OAT (°C)14.82kWh/hr per °C<0.001Cooling load sensitivity to outside-air temperature.
Occupancy (frac)236.40kWh/hr per unit<0.001Guest-driven internal gains + service loads.
OAT × Occupancy6.31interaction0.003Coupled sensitivity — hotter days with higher occupancy compound.
Illustrative demo — synthetic reference data. Not live customer or production data.